Understanding Cable Designations: YJV22, NYY, N2XH, and H07RN-F
News Details
One cable, four names
A copper conductor, XLPE insulated, PVC sheathed, 0.6/1 kV power cable is sold as YJV in China, N2XY in Germany, Cu/XLPE/PVC in a British specification, and something close to XHHW-2 in a North American one. The four names describe roughly the same job and not the same product.
That gap causes real money. A buyer substitutes on the strength of the code, the cable arrives dimensionally different, and the inspector rejects it against a standard nobody compared.
This guide decodes the codes most often seen in export enquiries, then shows where equivalence stops.
Decoding the GB and Chinese export code
The GB designation is built from position, not words. Each position says something about one layer.
| Letter or number | Meaning |
| YJ | Cross-linked polyethylene insulation (XLPE) |
| V | PVC insulation or sheath, depending on position |
| L | Aluminium conductor. Copper is the default and is not written |
| T | Copper, written only when clarity is needed |
| 22 | Steel tape armour with PVC outer sheath |
| 23 | Steel tape armour with PE outer sheath |
| 32 | Thin steel wire armour with PVC outer sheath |
| 33 | Thin steel wire armour with PE outer sheath |
| 42 | Thick steel wire armour with PVC outer sheath |
| WDZ | Low smoke, halogen-free, flame retardant |
| NH | Fire resistant, normally mica tape on the conductor |
| B | Single core building wire, fixed wiring |
| K | Control cable |
| R | Flexible conductor |
| P | Braid or tape screen |
Read left to right: insulation, conductor, armour, sheath. The first letter group is insulation, the armour digit comes last, and the outer sheath is implied by the armour code.
Five worked examples
| Designation | Construction | Typical use |
| YJV | Cu, XLPE insulation, PVC sheath, unarmoured | Indoor trays, cable ladders, protected routes |
| YJLV22 | Al, XLPE insulation, steel tape armour, PVC sheath | Direct burial, MV distribution |
| YJV32 3x185 | Cu, XLPE, thin steel wire armour, PVC sheath | Routes with tensile load or risk of impact |
| VV | Cu, PVC insulation, PVC sheath | LV fixed wiring, 70 °C conductor |
| WDZA-YJY | Cu, XLPE, halogen-free sheath, class A flame retardant | Metro, tunnel, hospital, public buildings |
The size suffix matters as much as the letters. In 3x185, the first number is the core count and the second is the cross section in square millimetres. A 3x185 does not mean three cores of 185 mm² total; it means three cores of 185 mm² each.
The European VDE code
German and much of continental European practice uses a letter system that reads differently.
| Code | Construction | Notes |
| NYY | Cu, PVC insulation, PVC sheath | 0.6/1 kV, unarmoured, the land cable baseline |
| NAYY | Al, PVC insulation, PVC sheath | Aluminium version of NYY |
| N2XY | Cu, XLPE insulation, PVC sheath | Higher temperature and current than NYY |
| NA2XY | Al, XLPE insulation, PVC sheath | Aluminium XLPE distribution |
| N2XH | Cu, XLPE insulation, halogen-free sheath | The common European LSZH construction |
| NYCWY | Cu, PVC, concentric copper wave screen | Where an earth screen must be continuous |
| NHXHX FE180 | Fire resistant, halogen-free | Circuit integrity for 180 minutes under DIN 4102-12 |
The N is a standard cable marker rather than a material. Y is PVC, 2X is XLPE, H is halogen-free. Once that mapping clicks, most European codes become readable.
British constructions
British specifications rarely use a code. They spell out the construction, and the standard number does the rest.
- Cu/XLPE/PVC/SWA/PVC to BS 5467, the workhorse armoured distribution cable.
- Cu/XLPE/LSZH/SWA/LSZH to BS 6724, the same cable with a halogen-free sheath for enclosed and public spaces.
- Cu/XLPE/PVC unarmoured to BS 7211 for tray and conduit routes.
- 6491X single core PVC building wire to BS 6004. BS 6387 CWZ is a fire resistance category rather than a cable type, and it is often quoted alongside BS 7846 fire resistant cable.
The point to hold on to is that BS 5467 armoured means steel wire armour. A GB 22 construction is steel tape. They are not the same mechanical protection, and a British engineer will notice.
North American types
North America names cable by insulation and application rather than by layer sequence.
- XHHW-2: XLPE insulation, rated 90 °C in wet and dry locations, widely used in conduit and trays.
- THHN/THWN-2: PVC insulation with a nylon jacket, 90 °C dry, 75 °C wet. RHW-2 / USE-2: rubber or XLPE, underground service and direct burial.
- MV-90 / MV-105: medium voltage cable at 90 °C or 105 °C conductor rating. TC-ER: tray cable with exposed run permission.
- Type W and G-GC: heavy duty trailing cable for mining and mobile equipment.
Sizes are AWG and kcmil. A 4/0 AWG is about 107 mm², and 250 kcmil is about 127 mm². Anyone converting by eye gets the size wrong by a step.
Cross-reference table
Use this as a starting point for a conversation, not as a substitution authority.
VDEIEC base| Construction | GB | British |
| Cu, PVC, PVC, unarmouredVVNYYCu/PVC/PVCIEC 60502-1 Al, PVC, PVC, unarmouredVLVNAYYAl/PVC/PVCIEC 60502-1 Cu, XLPE, PVC, unarmouredYJVN2XYCu/XLPE/PVC, BS 7211IEC 60502-1 Al, XLPE, PVC, unarmouredYJLVNA2XYAl/XLPE/PVCIEC 60502-1 Cu, XLPE, steel tape armour, PVCYJV22Rare in VDE rangeCu/XLPE/STA/PVCIEC 60502-1 Cu, XLPE, steel wire armour, PVCYJV32 or YJV42Rare in VDE range Cu/XLPE/SWA/PVC, BS 5467 IEC 60502-1 Cu, XLPE, halogen-free WDZ-YJY N2XH Cu/XLPE/LSZH, BS 8573 IEC 60502-1 Cu, XLPE, SWA, halogen-free WDZ-YJY32 Rare in VDE range Cu/XLPE/LSZH/SWA/LSZH, BS 6724 IEC 60502-1 |
XLPE insulated power cable
, put the standard and the construction on the same line of the comparison table. A price comparison across two different standards is not a comparison. Where equivalence breaks Five differences survive every tidy cross-reference sheet. Sheath and insulation thickness. Each national standard sets its own minimums. A cable that meets IEC can be thinner than the British equivalent, and an inspector measuring to BS will reject it. Armour type. Tape and wire armour behave differently under tensile load and under crush. They are not interchangeable even when the current rating matches. Conductor class and strand count. A Class 2 stranded conductor and a Class 5 flexible conductor of the same size terminate differently and bend differently. Temperature rating. PVC at 70 °C and XLPE at 90 °C change the derated current for the same copper. Substituting one for the other changes the protection setting. Approval route. A UL listing, a VDE certificate, a KEMA type test and a CPR declaration of performance answer different legal questions. An inspector at site accepts the one named in the specification. How to write a spec that cannot be substituted Three lines remove most of the risk: