Blogs /
Shipboard and Offshore Cable: Specifying to IEC 60092 and NEK 606

Shipboard and Offshore Cable: Specifying to IEC 60092 and NEK 606

Shipboard cable is specified by standards and class approval, not by part number. How tinned copper, SHF1 and SHF2 sheaths, braided armour and IEC 60332-3-22 Cat A decide acceptance.

News Details

What makes a marine cable different

At first look, a 0.6/1 kV shipboard power cable resembles a land cable of the same size. The differences are in the details that a classification society cares about: tinned copper instead of plain copper, a halogen-free sheath, a braided armour that also carries earth, and a fire test that is run on a bundle of cables rather than a single wire.

None of those choices is decorative. A vessel is a closed steel box with a single escape route, salt in the air, vibration in every frame, and no way to replace a riser at sea. Cable selection for marine work is written around those four facts.

The IEC 60092 stack in plain terms

Marine cable is governed by a family of standards rather than one document. Buyers who quote only a part number often miss the part that decides acceptance.

Standard What it covers
IEC 60092-350 General construction and test methods for shipboard power, control, instrumentation and data cable
IEC 60092-351 Insulating compounds
IEC 60092-352 Choice and installation of cables
IEC 60092-353 Power cable rated 1 kV and 3 kV
IEC 60092-354 Power cable rated 6 kV to 30 kV
IEC 60092-360 Sheathing compounds, including the SHF grades
IEC 60092-376 Control and instrumentation cable rated 150/250 V

A yard specification typically names the construction standard and the test standards together, for example 60092-353 with 60332-3-22 Cat A. Both parts need to match your offer.

Conductor: why tinned copper, not plain copper

Plain copper oxidises in salt air, and the oxide layer raises resistance at every terminal. Tinning protects the strand surface, keeps solderability, and holds resistance stable over years of humid operation. In marine work tinned copper is the default for power, control and instrumentation cable.

Two more conductor points come up in every technical review. Class 2 stranded is normal for fixed power cable, while Class 5 flexible is used where the cable enters a machine or a moving panel. And aluminium conductors, common on land distribution, are largely absent afloat, because of termination risk and weight balance in a hull that is already aluminium or steel.

Insulation and sheath: EPR, XLPE, SHF1 and SHF2

Insulation is usually EPR or a halogen-free XLPE. EPR is more forgiving of flex and heat cycling, which is why it dominates engine room and machinery space cable. XLPE offers lower dielectric loss and is common on higher voltage feeders.

Sheath grade Behaviour Where it is specified
SHF1 Halogen-free, low smoke, flame retardant, 90 °C General accommodation and machinery spaces
SHF2 As SHF1, plus resistance to drilling mud and oils Deck areas, offshore units, drilling packages
PVC Flame retardant but emits acid gas and dense smoke Largely excluded from enclosed spaces on modern vessels

The move from PVC to halogen-free sheath is not a fashion. In a fire inside a closed space, hydrogen chloride from PVC damages lungs and corrodes electronics in adjacent compartments, including the bridge. That is why SOLAS-related practice points to halogen-free constructions for cable in accommodation and essential circuits.

Mud resistance and NEK 606

NEK 606 is the Norwegian electrical committee specification widely used on offshore units and drilling vessels. Its practical addition over IEC is a sheath that survives contact with oil based drilling fluid. Standard halogen-free compounds swell and soften when exposed to mud, and a swollen sheath in a cable tray is a long term failure.

If your project is an offshore unit, a drillship, or a North Sea supply vessel, expect NEK 606 or an equivalent mud-resistant SHF2 requirement in the specification. For a merchant vessel or a ferry, IEC 60092 with SHF1 is normally enough.

Armour, screening and earth continuity

Most shipboard power cable carries a galvanised steel wire braid. The braid does two jobs: it resists mechanical damage in trays and at penetrations, and it provides a low impedance path for fault current when bonded at both ends.

Two details decide whether that works. The braid must be bonded to the gland and the gland to the bulkhead, or the earth path is decorative. And on single core AC cable, the armour must be non-magnetic, typically bronze or aluminium braid, or the cable will heat from induced circulating current in the armour itself.

Instrumentation and control cable in the same tray needs screening against the variable frequency drives that now run most pumps. That is a separate construction decision from power cable armouring, and mixing them up is a common cause of signal noise on commissioning.

Voltage classes and where each one is used

  • 150/250 V for control, instrumentation and alarm circuits, per IEC 60092-376.
  • 0.6/1 kV for the bulk of lighting, small power and distribution.
  • 1.8/3 kV for larger motors and thrusters on many vessels.
  • 3.6/6 kV to 12/20 kV for alternator feeders, bow thrusters and high voltage distribution on larger ships and offshore units.

The common error is treating 0.6/1 kV cable as suitable for a 3.3 kV circuit because the current rating looks fine. Voltage class is a dielectric requirement, not a thermal one.

Fire performance: the three tests that matter

IEC 60332-3-22, Category A is the bunched flame test used for shipboard cable. It burns a vertical rack of cable with a defined non-metallic volume per metre, and it is far more demanding than the single wire test in IEC 60332-1-2. A cable that passes the single wire test and fails Cat A is common, and it is not acceptable in a tray.

IEC 60754-1 and -2

measure acid gas. Halogen-free cable should sit at or near zero for hydrochloric acid emission, with low conductivity and pH within the limits of part 2.

IEC 61034-2

measures smoke density as light transmittance. Higher transmittance means a clearer escape route. For enclosed spaces and stairways this number matters as much as the flame result.
If the specification calls for circuit integrity during a fire, that is a fourth and separate requirement, with its own test regime and its own construction. It is not implied by Cat A.

Class society approval: what a certificate covers

Type approval from DNV, ABS, Lloyd's Register, Bureau Veritas, ClassNK, RINA, KR or CCS is usually a condition of supply. The certificate names the construction, the standard, and the range of sizes covered. Three checks keep it useful:

    Does the certificate cover the exact construction you are buying, including sheath grade and armour?
  • Is it a type approval for the product, or a factory approval for the works? They are different documents.
  • Is it still valid, and does the issuing society match the one named in the build specification?
  • Shenghua holds a CCS ship inspection certificate alongside ISO 9001, ISO 14001 and ISO 45001 system certification, and supplies marine and offshore constructions from its halogen-free and XLPE ranges. Details sit on the

    company profile page

    .
  • Procurement checklist for a marine order

      Construction standard, with edition, plus the test standards named separately
  • Conductor: tinned copper, class, and minimum strand count
  • Insulation and sheath compounds by grade, not by trade name
  • Armour type and whether it must be non-magnetic
  • Voltage class and the circuit it serves
  • Fire performance, including the bunched test category
  • Class society and the approval route
  • Temperature range, including cold bend if the vessel trades north
  • Drum length and marking, since marine stores are tight
  • Test documents, including routine reports per drum
  • Marine orders also carry shorter lead times than land projects, because a yard slot does not move. Confirm the drum plan and the certificate position before the keel block date, not after.
  • Frequently asked questions

    Can I use land cable on a vessel?

    Generally no. Plain copper, PVC sheath and single wire flame performance will fail a yard specification and a class review, even where the electrical ratings match.

    Is XLPE or EPR better for shipboard use?

    EPR is more tolerant of flex and thermal cycling, so it suits machinery spaces. XLPE suits fixed higher voltage feeders. Both are acceptable to the standards when correctly built.

    What does SHF2 add over SHF1?

    Resistance to drilling fluids and oils, which matters on offshore units. On a merchant ship it is usually unnecessary.

    Do I need a separate certificate for each size?

    Type approvals usually cover a size range within a construction. Check that your sizes fall inside the range rather than assuming they do.

    How is marine cable packed?

    Usually shorter lengths than land projects, on wooden or composite drums, with end caps and often with cable ties at both ends for pulling. Confirm drum weight against the yard crane.

    Standards referenced in this guide

      IEC 60092-350, -351, -352, -353, -354, -360 and -376, electrical installations in ships, issued by the International Electrotechnical Commission.
  • IEC 60332-1-2 and IEC 60332-3-22, flame propagation, issued by the International Electrotechnical Commission.
  • IEC 60754-1 and -2, acid gas emission, issued by the International Electrotechnical Commission.
  • IEC 61034-2, smoke density, issued by the International Electrotechnical Commission.
  • NEK 606, cables for offshore installations, issued by Norsk Elektroteknisk Komite.
  • IEC 60228, conductors in insulated cables, issued by the International Electrotechnical Commission.
  • For a yard package that mixes halogen-free power, control and instrumentation cable, see our

    LSZH cable range

    and the armoured constructions used where mechanical protection and earth continuity are both required. To check a specification against the class approval you need, send the cable list and the vessel or unit type.
  • Share to:
    facebook
    line
    Whatsapp
    Pinterest
    Tumblr
    Linkedin